PickettMotorv1.1

Motor starters, contactors and control circuits

🏠

Start a motor the way an electrician does

Switch on the isolator, press START and watch 24 V travel through the control circuit, pull in the contactor and spin the motor. Try reversing and star-delta, jam the load to trip the overload, then hunt down a hidden fault. Switch to Panel view to see the same circuit as real hardware on a DIN rail.

PICKETTECH PM-400 Motor starter trainer
FAULT ACTIVE400 V 3~ 50 Hz · 24 V DC control · M1 4 kW
PANEL DOOR
Q1 ONMain isolator / motor circuit breaker. Tap to switch.
M1 · stopped
0.0 A0.0 × FLC
0 rpmREADY
PEAK 0.0 A
F2
0%
CIRCUIT
BENCH
CONTROL CIRCUIT · 24 V DClive
POWER CIRCUIT · 400 V 3~carrying current

What's happening

Control circuit

Power circuit

How motor starters work

Eight short lessons. The buttons set up the trainer so you can see each idea, and the PickettPanel links let you wire it yourself.

⚡Control and power circuitsTwo circuits, one motor

A motor starter is really two circuits. The power circuit carries the heavy three-phase current (400 V here) from the supply to the motor. The control circuit is a separate low-power circuit, usually 24 V DC or 230 V AC, that decides when the power circuit is switched on.

The link between them is the contactor. A small current through its coil pulls in big contacts that switch the motor. Your finger is only ever on the 24 V side.

Why bother with two circuits?Pushbuttons, lamps and PLC inputs only need a tiny current, and 24 V is far safer to have on a panel door. It also means you can stop a 200 A motor with a button rated for 1 A.

On the trainer, the left screen is the control circuit and the right screen is the power circuit. Watch both when you press START.

KThe contactorCoil, main poles and auxiliaries

A contactor is a heavy-duty relay. When its coil (terminals A1 and A2) is energised, an electromagnet pulls every contact over at once:

  • Main poles 1-2, 3-4, 5-6 switch the three phases to the motor.
  • Auxiliary contacts are small contacts for the control circuit. A number ending in 3-4 is normally open (NO). A number ending in 1-2 is normally closed (NC).
MarkingMeaning
A1 – A2Coil
13 – 14Aux NO (closes when coil is on)
21 – 22Aux NC (opens when coil is on)

The first digit is just the position on the contactor: 13-14 is contact 1, 23-24 is contact 2, 43-44 is contact 4.

⟲The latch (holding contact)Why the motor keeps running

A START button only closes while you hold it. So how does the motor keep running when you let go? An auxiliary NO contact of the contactor itself (13-14) is wired in parallel with the START button.

  1. Press START: the coil energises and K1 pulls in.
  2. K1 13-14 closes, giving the coil a second path.
  3. Release START: current keeps flowing through 13-14. The contactor "holds itself in".
  4. Press STOP: the path breaks, the coil drops out and 13-14 opens again.
A built-in safety featureIf the supply fails, the coil drops out and the latch is lost. When power comes back the motor does not restart by itself. That's called no-volt release, and it stops machines leaping into life after a power cut.

This is exactly the start/stop rung you build in ladder logic: the output coil's own contact sits in parallel with the start input.

See it as a ladder rung
NCWhy STOP is normally closedFail-safe wiring

STOP buttons, overload contacts and emergency stops are all wired with NC contacts in series with the coil. Current must flow through them for the motor to run.

The reason is fail-safe design. If a stop wire breaks or a terminal works loose, the circuit opens and the motor stops. If STOP were an NO contact that had to close to stop the motor, a broken wire would leave you with a STOP button that silently does nothing.

The rule of thumbThings that start go in parallel (NO). Things that stop go in series (NC).

Real emergency stops go further: they have positively-driven contacts that are forced open mechanically, and they're often monitored by a safety relay.

FOverload protectionTripping before the windings cook

A fuse or MCB protects the cable against a short circuit, but a motor can be overloaded for minutes without blowing anything, slowly overheating its insulation. The thermal overload relay (F2) protects the motor itself.

  • It's set to the motor's full-load current (FLC) from the nameplate.
  • It heats up with current squared, so a big overload trips fast and a small one trips slowly.
  • Its 95-96 NC contact is in series with the coil and opens on a trip. Its 97-98 NO contact closes to light a trip lamp.
  • A Class 10 relay must trip within 10 seconds at 7.2 × its setting, which is about what a stalled motor draws.

A normal start draws 6 to 7 times FLC too, but only for a second or two, so the relay rides through it. A jammed rotor keeps drawing that current and the relay trips. After a trip the bimetal has to cool before RESET will work.

⇄Reversing and interlocksTwo contactors that must never meet

A three-phase motor turns the other way if you swap any two phases. A reversing starter uses two contactors: KF connects L1-L2-L3 straight through, and KR swaps L1 and L3.

If both contactors ever closed together, L1 and L3 would be connected straight to each other: a dead short between phases. So reversing starters are interlocked:

  • Electrical interlock: an NC contact of each contactor (21-22) sits in the other one's coil circuit. KF on means KR can't energise, and vice versa.
  • Mechanical interlock: a lever between the two contactors physically stops both closing at once.
  • Pushbutton interlock (optional): the FWD button's NC contact breaks the REV circuit.

Switch the interlocks off on the trainer, hold FWD, then press REV, and see what the circuit breaker thinks of it.

Y∆Star-delta startingCutting the starting current

Starting a big motor direct-on-line draws 6 to 8 times its full-load current, which can dip the supply and trip upstream protection. Star-delta starting reduces that.

  • Star (Y): the three winding ends U2, V2, W2 are joined. Each winding sees 400 ÷ √3 ≈ 230 V. Starting current and torque both drop to about one third.
  • Delta (∆): after a set time each winding is connected across two lines and gets the full 400 V for normal running.
I(star start) ≈ I(DOL start) ÷ 3     T(star start) ≈ T(DOL start) ÷ 3

Three contactors do the job: K1 (main), KY (star) and KD (delta), with a timer KT doing the changeover. KY and KD are interlocked because closing both together would short the supply.

The catchWith only a third of the torque, star-delta suits fans, pumps and machines that start light. A loaded conveyor might not get up to speed in star. Note the current spike at the switch to delta: compare the PEAK reading with a DOL start.
🔒Safe isolationDead means proven dead

Pressing STOP does not make a machine safe to work on. The power circuit up to the contactor is still live, and a fault or another person could start it. Before working on a motor circuit, electricians follow a safe isolation procedure:

  1. Identify the correct isolator for the equipment.
  2. Switch it off and lock it off with your own padlock. Add a warning tag.
  3. Prove your voltage tester works on a known live source or proving unit.
  4. Test that the circuit is dead, between all phases and between each phase and earth.
  5. Prove the tester again, so you know it didn't fail during the test.
This trainer is for learning circuit principles. Only work on real installations if you're trained and authorised, and follow your local wiring rules (the ETCI National Rules in Ireland, BS 7671 in the UK) and your site's lock-out/tag-out procedure.

Fault finder

Load a hidden fault into the DOL circuit. Work the buttons, watch what the motor and lamps do, then turn on PROBE and tap points on the control screen to measure the voltage.

How to fault-find like a pro: first note the symptom (what works and what doesn't). Then measure from the supply towards the coil. The fault lies between the last point where you read 24 V and the first point where you read 0 V.

No fault loaded.

What's wrong? Pick an answer when you think you know.

Now wire it yourself in PickettPanel

Reading a circuit is one skill. Wiring it is another. Open PickettPanel and build each starter from scratch, then test it.

CHALLENGE 1 · BEGINNER

DOL start/stop

  1. Feed 24 V through an overload NC contact and a STOP (NC) button.
  2. Add a START (NO) button to the contactor coil.
  3. Put a K1 NO contact in parallel with START.
  4. Add a RUN lamp on another K1 NO contact.
Build it in PickettPanel ↗
CHALLENGE 2 · INTERMEDIATE

Forward/reverse

  1. Build two latching rungs, FWD and REV, sharing one STOP.
  2. Put KR's NC contact in the KF coil circuit, and KF's NC in KR.
  3. Test: with FWD running, REV should do nothing until you press STOP.
Build it in PickettPanel ↗
CHALLENGE 3 · ADVANCED

Star-delta with timer

  1. Latch the main contactor K1 and energise timer KT with it.
  2. Feed KY through KT's timed NC contact and KD's NC interlock.
  3. Feed KD through KT's timed NO contact and KY's NC interlock.
Build it in PickettPanel ↗

Motor current calculator

Estimate full-load current, starting current and the overload setting for a three-phase motor. Always use the nameplate FLC when you have it.

Full-load current—
DOL starting current—
Star-delta starting current—
Input power—
Overload setting (DOL, reversing)—
Overload in the windings (star-delta)—
Synchronous speed (4-pole, 50 Hz)1500 rpm
Typical full-load speed≈ 1440–1460 rpm

Starting current is shown as the usual 6 to 8 × FLC range. If the star-delta overload sits in the motor windings (after the main contactor) it only sees phase current, so it's set to FLC ÷ √3 ≈ 0.58 × FLC.

Terminal markings and device letters

The labels you'll find on real contactors, overloads and drawings.

MarkingWhat it isWhere you'll meet it
A1 – A2Contactor or relay coilControl circuit. A1 normally goes to the switched supply side.
1/L1 – 2/T1Main pole (also 3/L2 – 4/T2, 5/L3 – 6/T3)Power circuit. L is the supply side, T goes to the motor.
13 – 14Auxiliary NO contact (any x3 – x4)Holding contacts, run lamps, PLC run feedback.
21 – 22Auxiliary NC contact (any x1 – x2)Interlocks between reversing or star-delta contactors.
95 – 96Overload NC contactIn series with the coil. Opens on a trip.
97 – 98Overload NO contactTrip lamp or PLC fault input.
55 – 56 / 67 – 68Timed NC / timed NO contactTimer contact blocks, such as the star-delta changeover.
U1 V1 W1 / U2 V2 W2Start and end of each motor windingMotor terminal box. Links set star or delta.
K · S · F · H · MContactor/relay · switch/button · protection · indicator · motorDevice letters on drawings. Newer IEC 81346 drawings may label power contactors Q.

Check yourself

Six questions. Pick an answer to see the explanation.

Formula sheet

I = P / (√3 · V · pf · η)Full-load current of a three-phase motor
P = √3 · V · I · pfThree-phase input power
V(star) = V(line) / √3Voltage across each winding in star
I(Y start) ≈ I(DOL) / 3Star-delta starting current
n(sync) = 120 · f / pSynchronous speed (p = number of poles)
slip = (n(sync) − n) / n(sync)How far the rotor lags the field